| Temperature-rise |
| UL have carried out tests on complete switchboards up to 5000A. The temperature-rise did not exceed 65K with tin plated copper bars or 50K with none plated copper bars. Likewise, the temperature-rise in motor starter units did not exceed maximum limit. |
| Verified by: |
|
Underwriters Laboratories Inc. |
| Dielectric voltage withstand |
|
The CUBIC modular system has been tested to 2.2 kV for 1 minute without breakdown. The tests were carried out between: |
| Verified by: |
|
Underwriters Laboratories Inc. |
| Short circuit withstand |
|
The CUBIC busbar systems up to 5000A (S7000) have been tested by UL. |
| Verified by: |
|
Underwriters Laboratories Inc. |
| Grounding and bounding |
| In CUBIC assemblies the effective connection between the exposed conductive parts has been tested by UL. The resistance between the ground bus and either an exposed dead metal or the ground contact was tested to be less than 0.1 ohm. Likewise, the resistance between the ground bus and the grounding contacts was measured to be less than 0.005 ohm. |
| Verified by: |
|
Underwriters Laboratories Inc. |
| Spacings |
| The spacing through air and over surface is made such that it can be verified for up to 600 V in CUBIC assemblies. |
| Verified by: |
|
Underwriters Laboratories Inc. |
| Environmental rating |
|
The CUBIC modular system is in standard version tested by UL to type 1,2 5 and 12 |
| Verified by: |
|
Underwriters Laboratories Inc. |
| Main type-tested electro-technical data. |
| Rated voltage and frequency: Up to 600 V; 50-60 Hz Rated current: Up to 5000 A Bus short circuit bracing: Up to 100 kAmp RMS Enclosure types Type 1,2,5,12 |
| Verified by: |
|
Underwriters Laboratories Inc. |